BOLZTHERM® SW-50 is suitable for use in the liquid phase in closed, non-pressurised heat transfer systems with forced circulation in a temperature range of -60 °C to 200 °C, provided that the maximum film temperature of 230 °C is not exceeded. The optimal operating range is between 50 °C and 180 °C. For applications outside the optimal operating range, please contact us for consultation.
| Typical properties | Unit | Standard | Value |
|---|---|---|---|
| Operating range | [°C] | - | -60 to 200 |
| Max. flow temperature | [°C] | - | 200 |
| Max. film temperature | [°C] | - | 230 |
| Viscosity at 40 °C | [mm²/s] | DIN 51562-1 | 4.00 |
| Viscosity at 100 °C | [mm²/s] | DIN 51562-1 | 1.95 |
| Density at 20 °C | [kg/m³] | DIN 51757 | 919 |
| Pour point | [°C] | DIN ISO 3016 | <-100 |
| Flash point | [°C] | DIN EN ISO 2719 | >120 |
| Flash point | [°C] | DIN EN ISO 2592 | >120 |
| Acid number | [mg KOH/g] | DIN ISO 6618 | ≤ 0.2 |
| Carbon residue | [wt.-%] | DIN EN ISO 10370 | < 0.1 |
| Initial boiling point at 1013 mbar | [°C] | - | >220 |