Skip to content

Bolztherm CW-100

BOLZTHERM® CW-100 is suitable for use in the liquid phase in closed, non-pressurised heat transfer systems with forced circulation in a temperature range of -6 °C to 330 °C. The maximum film temperature of 340 °C must not be exceeded.

Typical propertiesUnitStandardValue
Operating range[°C]--6 to 330
Max. flow temperature[°C]-330
Max. film temperature[°C]-340
Viscosity at 40 °C[mm²/s]DIN 51562-1113
Viscosity at 100 °C[mm²/s]DIN 51562-111.5
Density at 20 °C[kg/m³]DIN 51757877
Pour point[°C]DIN ISO 3016-6
Flash point[°C]DIN EN ISO 2719>250
Flash point[°C]DIN EN ISO 2592260
Acid number[mg KOH/g]DIN ISO 6618≤ 0.2
Carbon residue[wt.-%]DIN EN ISO 10370< 0.1
Initial boiling point at 1013 mbar[°C]->360

More information (downloads):

Safety data sheet:
Safety data sheet

Technical data sheet:
Please enter your e-mail address to download the technical data sheet.
Technical data sheet (German)